28m³ DOUBLE-WALL PRESSURE TANK
The 28m³ double-walled steel pressure tank from Rain for Rent offers the best possible protection for all projects that require the storage of (non-)flammable liquids, alkaline, acidic or other liquids.
The double-walled and pressure-resistant construction allows the user to safely and easily handle critical liquids that pose a particular challenge


FEATURES & BENEFITS
- Double-walled construction for maximum environmental protection
- Pressure-resistant up to 10.0 (+/-0.15) bar for maximum occupational safety
- Electrically conductive inner coating with resistance to (non-)flammable liquids, acidic or alkaline liquids
- Quick and easy delivery and installation without a crane or other lifting equipment
- Variable connection options for filling and emptying
- Maximum work safety
- Easy inspection and cleaning
APPLICATION EXAMPLES
Wide range of applications for the storage of liquids with low flash points:
- Storage of products and mixtures
- Waste and process streams
- Rinsing water from cleaning work
- Liquids from accidents
CERTIFICATION AND TESTING
- Testing according to Directive 2014/68/EU for fluid group 1
- CE conformity
Dimensions & Construction | |
Dimensions: | 2,680 x 7,464 mm (transport); 3,780 x 7,464 mm (installed) |
Transport: | Roll-off hook lift according to DIN30722 |
Material: | P355GH/P265GH |
Tank weight empty: | 10,000 kg |
Total weight empty: | 10,200 kg |
Operating weight: | max. 54,600 kg |
Density of medium: | max. 1,600 kg/m³ |
Medium state: | liquid / gaseous |
Filling volume: | 27,750 L |
Pressure limits tank: | -0.15 PS/+10 bar |
Pressure limits jacket: | -0.15 hp/0.1 bar |
Temperature limits: | -10/+70 |
Features | |
Connections: | DN100 PN 16 cleaning nozzle (front); 1x DN150 PN16, 2x DN100 PN16, 1x DN50 PN16, 1x DN80 PN16 (roof) |
Stairs / railings: | Access ladder and walkway (passenger side) |
Inspection access points: | DN600 (with swivel arm) and DN300 dome cover (roof) |
Monitoring: | DN100 rupture disk (10 bar) / pressure and vacuum gauges |
Internal coating: | chemical-resistant 2-component epoxy resin coating |
External coating: | Weather-resistant external coating |
Level Gauge: | Roof-mounted dial gauge (optional) |
Application media: | flammable liquids, acidic and alkaline liquids, others on request |
Building tests: | DGRL/68/EU; AD2000 |
Pressure tests: | 14.8 bar / -0.15 bar |
Inspections: | Pressure and vacuum test before and after use, regular hydrostatic pressure test, tests in accordance with legal and manufacturer specifications |